500-7500kVA Three-phase Pad-mounted Transformer

Three-phase pad-mounted transformers is oil-filled,three-phase,commercial pad mounteddistribution transformer specifically designed for outdoor installation on a concrete pad and provideunderground power distribution to commercial,industrial and institutional loads.It is availablein both livefront and dead front construction,for radial feed and loop feed applications,with or without taps,thetransformer uses aluminum or copper winding and is optimized to maximize efficiency and footprint.It hasma…

SKU: 57TPP-151

Description

Three-phase pad-mounted transformers is oil-filled,three-phase,commercial pad mounteddistribution transformer specifically designed for outdoor installation on a concrete pad and provideunderground power distribution to commercial,industrial and institutional loads.It is availablein both livefront and dead front construction,for radial feed and loop feed applications,with or without taps,thetransformer uses aluminum or copper winding and is optimized to maximize efficiency and footprint.It hasmany advantages:such as high voltage,no drifting of neutral point,low loss,small volume,cost-effective,safety and environment protection and etc.


Standard Features

·50 Hzor 60 Hz operation.


·65℃ average winding rise.


·Radial&loop feed arrangements.


·Dead and live front type of HVterminals.


·Bolted-on cabinet with removable sill having the following depths:


-19″deep for 300kVA through 750 kVA

-22″deep for 1000kVA through 1500kVA

-24″deep for 2000 kVA through 3750kVA

-30″deep for 5000 Kva through 7500kVA

·Tank:Mild steel


·Steel HV/LV compartment barrier


·Padlocking facilitywith penta-head bolt on the HVand LV,Three-point latching mechanism.


·HVand LV compartment doors-hinged and lift-off type with 120°holding bars


·Stainless steel door hinges


·Removable sillfor easy installation


·Three-point latching door for security


·Permanent Nameplate per ANSI requirement.


·ANSI tank ground pads.


·One-inch drain valve and sampler.


·Self-actuating pressure relief valve.


·Four(4)lifting lugs


·Welded cover with hand hole


·Oil fll plug


·Removable LV neutral ground strap;as required


·Durable,corrosion-resistance powder coat paint finished Munsell Green 7GY3.29/1.5


·Designed,manufactured and tested in accordance with the latest ANSI and IEEE standards.

Hangzhou Giantway Import & Export Co., Ltd. 
DATA SHEET OF PAD-MOUNTED TRANSFORMER
(Copy right: HZGW)
Project Name
S/N Description Unit
1 Rated capacity kVA 1000 1500 2000 2500 3000
2 HV/Primary V 13800V Delta 13800V Delta 13800V Delta 13800V Delta 13800V Delta
3 LV/Secondary V 400V – Wye 400V – Wye 400V – Wye 400V – Wye 400V – Wye
4 Transformer Feed Type Loop Loop Loop Loop Loop
5 Tap changer NO-Load,5step,±2*2.5%, NO-Load,5step,±2*2.5%, NO-Load,5step,±2*2.5%, NO-Load,5step,±2*2.5%, NO-Load,5step,±2*2.5%,
6 vector group Delta-Wye Delta-Wye Delta-Wye Delta-Wye Delta-Wye
7 Material of coil Copper Copper Copper Copper Copper
8 Material of core Silicon steel Silicon steel Silicon steel Silicon steel Silicon steel
9 No. of Phases 3 3 3 3 3
10 Frequency (Hz) 60 60 60 60 60
11 Insulation Fluid Mineral Oil Mineral Oil Mineral Oil Mineral Oil Mineral Oil
12 Insulation Class A A A A A
13 Rated impedance % 5.75 5.75 5.75 5.75 5.75
14 No-load loss at 20℃ W 996 1532 1782 2438 5385
16 full load loss at 85℃,100%load W 7832 9880 12987 14356 28450
17 Total Losses at 85°C 8828 11412 14769 16794 33835
18 Efficiency at 100% load % 99.12 99.24 99.27 99.33 98.88
Standard(s) IEEE C57/DOE2016
19 Temperature rise
Oil surface temperature rise K 60 60 60 60 60
Average winding temperature rise K 65 65 65 65 65
Hotest point  temperature rise K / / / / /
20 Basic lightning impulse insulation level(BIL)
HV kV 95 95 95 95 95
LV kV
23 Noise level dBA 62 62 62 62 62
24 Ambient temperature ℃ Maximum Ambient Temp.  40℃ Maximum Ambient Temp.  40℃ Maximum Ambient Temp.  40℃ Maximum Ambient Temp.  40℃ Maximum Ambient Temp.  40℃
25 Method of cooling ONAN ONAN ONAN ONAN ONAN
26 Enclosure Rating: NEMA 3R Weatherproof,Munsell™ 7.0 GY 3.29/1.5 Bell green NEMA 3R Weatherproof,Munsell™ 7.0 GY 3.29/1.5 Bell green NEMA 3R Weatherproof,Munsell™ 7.0 GY 3.29/1.5 Bell green NEMA 3R Weatherproof,Munsell™ 7.0 GY 3.29/1.5 Bell green NEMA 3R Weatherproof,Munsell™ 7.0 GY 3.29/1.5 Bell green
27 Housing Type Compartmental Air-Filled Cabinet w/ Locking Doors, HV Compartment Left, LV Compartment Right, Steel Barrier Separation,Weatherproof and UV Resistant Epoxy Coating and Undercoating Compartmental Air-Filled Cabinet w/ Locking Doors, HV Compartment Left, LV Compartment Right, Steel Barrier Separation,Weatherproof and UV Resistant Epoxy Coating and Undercoating Compartmental Air-Filled Cabinet w/ Locking Doors, HV Compartment Left, LV Compartment Right, Steel Barrier Separation,Weatherproof and UV Resistant Epoxy Coating and Undercoating Compartmental Air-Filled Cabinet w/ Locking Doors, HV Compartment Left, LV Compartment Right, Steel Barrier Separation,Weatherproof and UV Resistant Epoxy Coating and Undercoating Compartmental Air-Filled Cabinet w/ Locking Doors, HV Compartment Left, LV Compartment Right, Steel Barrier Separation,Weatherproof and UV Resistant Epoxy Coating and Undercoating
28 Others requirements / / / / /
29 nameplate YES YES YES YES YES
30 package Export wooden crate Export wooden crate Export wooden crate Export wooden crate Export wooden crate
31 dimension (width*depth*heigh) mm
32 weight KG
33 Altitude: m <1000 <1000 <1000 <1000 <1000
34 manual YES YES YES YES YES
language English English English English English
Accessories Manual English English English English English
35 Accessories
Fill&Drain & Sample Valve YES
Load Break Switch YES
Thermometer YES
Liquid Level Gauge YES
Pressure Vacuum Gauge YES
Pressure Relief Valve YES
Rating & Diagram Plate YES
Internal Weak Link Fuses with CLFs YES