The Type of XS Dehydrating Breather

Dehydrating breather is a device used to remove moisture and desiccate the air within transformers or oil conservators of mutual inductors, Installed in the air inlet port of transformers or oil conservators of mutual inductors, it mainly works to keep the transformer oil dry and clean.
CONSTRUCTION
The top and the bottom sections are casted aluminum and electrostatic powder painted. The shafts are made of nickel plated steel and the sieves are made of zinc sheet. Container cylinder is glass or …

SKU: TTOXD-195

Description

Dehydrating breather is a device used to remove moisture and desiccate the air within transformers or oil conservators of mutual inductors, Installed in the air inlet port of transformers or oil conservators of mutual inductors, it mainly works to keep the transformer oil dry and clean.

CONSTRUCTION

The top and the bottom sections are casted aluminum and electrostatic powder painted. The shafts are made of nickel plated steel and the sieves are made of zinc sheet. Container cylinder is glass or polycarbonate depending on the customers’ request. Oil bowl is of polycarbonate and the bowl holder is made of CrNi material.

OPERATION PRINCIPLE

When the transformer gets air in, an air flow from and to the oil bowl occurs. The oil layer in the bowl prevents the dryer material from continuous contact with the damp external air and cleans the air flowing in. If the operation temperature of the transformer decreases, the volume of the isolation oil gets smaller. During this lessening, an amount of air equal to the lessening amount is absorbed in to the oil bowl through air holes. This air then transfers to the expansion vessel and contacts with the oil layer. During this transfer, air contacts with the dryer material and leaves its moisture there. With the heating of the oil in the transformer tank, the air inside flows out from the opposite direction of the moisture holder. 

Technical parameter & external dimension

Code Type  D H Silicagel
weight(KG)
For transformer
oil(KG)
Transformer capacity
(KVA)
YC.683.1 XS1—0.2 80 160(square flange)
150(round flange)
0.2 700 Below 80KVA
YC.683.2 XS1—0.5 100 180(square flange)
160(round flange)
0.5 1500 Below 200KVA
YC.683.3 XS1—1 100 260 1 3500 Below 630KVA
YC.683.4 XS1—1.5 140 250 1.5 5000 Below 2000KVA
YC.683.5 XS1—2 140 280 2 7000 Below 3150KVA
YC.683.6 XS1—3 165 290 3 10000 Below 10000KVA
YC.683.7 XS1—5 165 370 5 22000 Below 50000KVA
YC.683.8 XS1—10 165 610 10 35000 Below 500000KVA

Note: Flange installation method is selected by the customer, such as circular installation, add C after the code. For square installation, add S at the back. The type of silicone use is also specified by the customer.