Gas Relay

SKU: GR-189

Description

Gas relay sedrles QJ are kinds of protective devices installed on oil immersed transformers with on load tap changers of 800KVA and above, it is mocented on the connecting pipe between transformer and oil conservator. When the stop plate of gas relay is rushed by gas or heavy oil flow  caused by internal failure of transformer or on load tap changer,the tripping contacts will be closed and the power source be disconnected automatically to providea protection for transformer or on load tap changer.

Model Explanation 

QJ: □-□

QJ: gas relay

□:Serial number
□:Nominal dia mm

Voltage Regulation Model

I.Main specifications 

Type fig Installing dimension Remarks
D D1 D2 D3 D4 B L1 L H1 H2 n d
QJ4-25 fig1  25   85 115   31   56 200 206 210 150   4 14 There are 4 binding posts that can be Connect the air box. (1)
QJ6 -25  25   85 115   31   56 200 206 186 141 14

2 binding posts, no gas

alarm signal (2)

QJ1-50 fig2  50 130 56 100 120 160 168 216 156   4 M12

This product is an old model, rarely used except for maintenance, with 4 terminals. The trip contacts are connected in series, and there is no gas box interface. (3)

QJ1-80  80 130 85 110 120 160 168 216 156   4 M12
QJ10-50  50 130 56 100 120 160 168 216 156   4 M12

This product is a replacement product of QJ1-50 and QJ1-80, with the same installation size,parallel connection of trip contacts, and air guide box can be installed. (4)

QJ10-80  80 130 85 110 120 160 168 216 156   4 M12
QJ3-50  50 125 125 185 223 160   4 14 This product is used on oil-immersed transformers with fire extinguishing device, 6 terminals, and can be installed with gas guide box. (5)
QJ3-80
QJ12-80
 80 160 160 185 240 160   4 18
QJ4-50  50 125 125 185 223 160   4 14 5 terminal posts, the trip contacts are connected in parallel, and the gas guide box can be installed. (6)
QJ4-80  80 160 160 185 240 160   4 18

Technical data

1、Working temperature:-30℃~95℃

2、Switch capacity:AC 220V 0.3ACOSφ≤0.6 DC220V0.3AS≤5×10-35

Type QJ-80 QJ-50 QJ-25
Range of flow(m/s) 0.7~1.5 0.6~1.2 0.8~1.2
Gas accumulaton 250~300 <250

Filling transformer oil into the relay, Pressurizing normal temperature 200Kpa, Continued200min and without any leakage.

Test Item Voltage between
Contacls
Woleage between
terminal and earth
Voltage berween signal
and tripping terminal

Withstand power frequency

voltage and time

2000v/1min 2000v/1min 2000v/1min

Our Advantage

* Big range of gas detection 
* Low oil level alarm Removal function

* Probe detection

* Direct oil Display

* responsive

* Stable use

* Stainless-steel float,anti-aging,floats accurately